Skip to content

End stop issue using closed loop motors

https://logbook.virgo-gw.eu/virgo/?r=66874


When the motors reach the end-stops, the step counter on the VPM freezes and displays unrealistically large numbers (10–11 digits). To recover the functionality, the following manual procedure is required:

  • Access the actuator physically.
  • Rotate it in the opposite direction (away from the end-stop).
  • Power-cycle the motor driver in the TCS room.
  • Restart the VPM process.

Only then it is possible to control the motors remotely again.

Edited by Emmanuel Pacaud