End stop issue using closed loop motors
https://logbook.virgo-gw.eu/virgo/?r=66874
When the motors reach the end-stops, the step counter on the VPM freezes and displays unrealistically large numbers (10–11 digits). To recover the functionality, the following manual procedure is required:
- Access the actuator physically.
- Rotate it in the opposite direction (away from the end-stop).
- Power-cycle the motor driver in the TCS room.
- Restart the VPM process.
Only then it is possible to control the motors remotely again.
Edited by Emmanuel Pacaud